Designed for direct or indirect measurement of 1-phase network parameters: U, I, f, P, Q, S, PF, tg fi, fi, Ep, Eq. Thanks to modern design, N27P fulfills the requirements for devices mounted in standard modular switchgears.
Features:

universal measuring input:

1/5 A 100/400 V a.c.
32/63 A, 100/400 V a.c.

direct measurement (up to 63A),
output:

RS-485 interface  with MODBUS protocol,
1 x relay + 1 x analog or 2 x relay,

modern graphical display in OLED technology,
programmable current and voltage transformer rati os,
meter configuration using button or free eCon software (through USB),
external dimensions: 53 x 110 x 60mm.

SPECIFICATIONS

Measured values and ranges

Measured Value

Range

Basic Error

Current in
 
1A
5A
32A*
63A*

 
 
0.005>1.200A AC
0.025>6.000A AC
0.160>38.40A AC
0.315>75.60A AC

+/- 0.2%

Voltage L-N
 
100V
400V

 
 
5>120V
20>480V

+/-0.2%

Frequency (f)

45.0>66.0>100Hz

+/-0.2%

Active power (p)
 
Version – 1/5A
Version – 32/63A
 

 
 
-2.88 kvar>1.00 var>2.88 kvar
-32.29 kvar>1.00 var>32.29 kvar

+/-0.5%

Reactive power (Q)
 
version 1/5A
version 32/63A

 
 
-2.88 kvar>1.00 var>2.88 kvar
-32.29 kvar>1.00 var>32.29 kvar

Apparent power (S)
 
version 1/5 A
version 32/63 A

 
 
1.40 VA>2.88 kVA
1.40 VA>32.29 kVA

PF

-1>0>1

Tangensφ

-1.2>0>1.2

+/-1%

φ

0.359

Active energy (Ep)

0>999 999.9 kWh or 9 999.999 MWh

+/-0.5%

Reactive energy (Eq)

0>999 999.9 kvarh or 9 999.999 Mvarh

*concerns the version for direct measurement

 

Outputs

Output type

Description

Relay

1-2 x (depending on the meter version) programmable relay output, NOC, load capacity 250 V~/0.5 A~, number of cycles 1 x 10

Analogue

lack or 1 x (depending on the meter version) programmable analog output 0/4..20 mA, Rload = 0…250Ω

 

Digital Interface

Interface type

Transmission protocol

Mode

Baud rate

RS-485

MODBUS RTU

8N2, 8E1, 8O1, 8N1

4.8; 9.6; 19.2; 38.4; 57.6; 115.2 kbit/s

USB1.1/2.0

8N2

9.6 kbit/s

 

External Features

Readout field

OLED display

 

Overall dimensions

53x110x60 mm

mounting on a 35mm DIN rail

Weight

0.2 kg

 

Protection grade

for housing: IP40

for terminals: IP00

 

Rated Operating Conditions

Power supply

85>253 V a.c. 40…400 Hz / 90>300 V d.c.

Power consumpti on: in supply circuit <5 VA in voltage circuit <0.2 VA in current circuit: for undirect meas. <0.05 VA, for direct meas. <2.5 VA Temperature ambient: -10…23…55°C storage: -30…70°C Relative humidity 25 … 95% inadmissible condensation Working position vertical   Standard conversion time 1.2s   Maximum conversation time 2.2s   Preheating time 15min   External magnetic field 0>40.400A/m

 

Short duration overload (1s)

voltage input: 2 UN (max. 1000 V)

current input: 10 IN

Sustained overload

voltage: 1,2 UN

current: 1,2 IN

 

Safety & Compatability Requirements

Electromagnetic compatibility

noise immunity

acc. to EN 61000-6-2

noise emissions

acc. to EN 61000-6-4

Isolati on between circuits

basic

acc. to EN 61010-1

Polluti on level

2

Installati on category

III (for voltages above 300 V – category II)

Maximal phase-to-earth working voltage

– for supply circuits 300 V
– for measuring input 600 V – cat. II (300 V – cat. III)
– for other circuits 50 V

Altitude above sea level

< 2000 m