AC Parameter Digital Panel Meter, N20Z – available on request
Description
PRODUCT DESCRIPTION
The N20Z meter is a digital programmable panel instrument destined for measurements of a.c. voltages, a.c. currents, or frequency. The readout display is a LED display which enables the exposition of results in red, green or orange colour.
Parameters of the N20Z meter:
input:
? a.c. current: 1 A, 5 A,
? a.c. voltage: 100 V,?250 V, 400 V?
? frequency: 20?500 Hz.
2 alarm outputs of OC type (4 types of alarms)?signaled by highlight of the alarm index,
protection level ensured by the housing: IP65,
readout field: 5 three-colour LED displays of 14 mm?height,
highlighted measuring units,??
supply: 85?253 V a.c./d.c. or 20?40 V a.c./d.c.
overall dimensions: 96 x 48 x 64 mm.
For the configuration of the N20Z is destined LPConfig program. The meter must be connected with the PC computer through a PD14 converter.
Parameters which can be reprogrammed are as follows:
display colour, individually in three intervals,
thresholds of displayed overflows,
display precision of the result (decimal point),
highlight of the unit,
kind of the measured signal a.c. or a.c. + d.c. (True RMS),
averaging time of the measurement,
recounting of indications (individual characteristic),
two alarms of OC type operating in six working modes.
SPECIFICATIONS
Measuring ranges
INPUTS:
Measuring range of Un voltage:
1?100?120 V
2.5? 250?300 V
4? 400?480 V
input resistance > 2 M?
Measuring range of In current:
0.01? 1?1.2 A
0.05? 5?6 A
input resistance 50 m? ? 10%
input resistance 10 m? ? 10%
Frequency measusurement:
(in voltage range 24? 480 V)
20? 500 Hz
input resistance > 2 M?
Preheating time
30 min.
Intrinsic error (at manufacturer settings):
? voltage and current
? (0.5% of the range ?1 digit)
in the frequency interval
20? 500 Hz
? frequency
? (0.02% of the range ?1 digit)
Additional errors in rated operating conditions:
? from ambient temperature changes
(50% of the intrinsic error/10K)
Averaging time:
? voltage, current (programmable)
min 0.5s (1s by default)
? frequency (not programmable)
1s
Alarm outputs
outputs of O/C type
(30 V, 20 mA),
Passive outputs acc. to
EN 62053-31
Rated operating conditions:
? supply voltage
85?253 V a.c. (45?65 Hz) or d.c.
20?40 V a.c. (45?65 Hz) or d.c.
? ambient temperature
? 10?23?55?C
? storage temperature
? 25? + 85?C
? relative air humidity
< 95%
(condensation inadmissible)
? working position
any
Sustained overload capacity
120% Un, 120% In
Short duration overload capacity (3 s):
? voltage input
2 Un (< 1000 V)
? current input
10 In
Readout field
5-digit three-colour LED display:
? digit height: 14 mm,
? colours: green, orange, red,
? indication range: -19999?99999
Ensured protection level from frontal side
IP 65 acc. to EN 60529
Dimensions
96 x 48 x 64 mm (with terminals)
Panel cut-out dimensions
92+0.6 x 45+0.6 mm
Weight
< 0.25 kg
Power consumption
< 6 VA
Electromagnetic compatibility:
? noise immunity
acc. to EN 61000-6-2
? noise emission
acc. to EN 61000-6-4
Safety requirements acc. to PN-EN 61010-1:
? isolation between circuits
basic
? installation category
III
(for 400 V execution ? category II)
? pollution degree
2
? maximal phase-to-earth working voltage:
?
? for supply circuit
300 V
? for measuring input
600 V ? category II
600 V ? category II
? for input destined for programming
50 V
Reviews