AC Signal Transducer (Curreent), P20Z – available on request
Description
PRODUCT DESCRIPTION
Measuring transducer P20Z type is destined to a continuous conversion of the rms current value or alternating voltage without the constant component into a standard d.c. current or d.c. voltage signal.
The transducer output signal is galvanically insulated from the input signal and the supply.
Features:
input: 0?60 / 100 / 150/ 250/ 400 / 500 / 600 V a.c., 0?1 / 5 A a.c.,
output: 0/4?20mA, 0?10V.
External dimensions: 22,5 x 120 x 100mm
?
SPECIFICATIONS
Basic parameters:
input voltage
60, 100, 150, 250, 400, 500, 600 V a.c.
input current
1 A (X/1 A a.c.), 5 A (X/5 A a.c.)
output signal
0?5 mA Rload ? 2000 ?
0?20 mA Rload ? 500 ?
4?20 mA Rload ? 500 ?
0?10 V Rload ? 500 ?
response time
0.5 sek.
accuracy class
0.2
transducer preheating time
15 min.
Consumption:
in supply circuit
? 4 VA
in voltage circuit
? 0.6 VA
in current circuit
? 0.2 VA
Supply voltage
85? 253 V a.c./d.c. or
20? 40 V d.c. or a.c.
Protection level ensured:
by the housing
IP 50
from the terminal side
IP 20
Weight
0.125 kg
Overal dimensions
22.5 x 120 x 100 mm
Fitting
on a 35 mm rail
Maximal wire section
2.5 mm2 for executions with screw socket-plug terminals
1.5 mm2 for executions with inseparable screw terminals
Reference and rated operating conditions:
input signal
0?0.01?1.2 In; 0?0.01?1.2 Un
frequency of the input signal
45?65?500 Hz
supply
85? 253 V a.c./d.c. or
20? 40 V d.c. or a.c.
admissible peak factor:
current
2
voltage
2
ambient temperature
? 20?23?55?C
storage temperature
? 25?+85?C
relative humidity
? 95%
(inadmissible condensation)
external magnetic field
0?40?400 A/m
short duration overload
(5 s)
voltage input
2 Un (max.1000 V)
current input
10 In
working position
any
Additional errors:
In multiplicity of the class index:
from ambient temperature changes
< 0.5 k/10 K
external magnetic field
< 1 k
frequency of the input signal
< 1 k/100 Hz
Standards fulfilled by the transducer:
Electromagnetic compatibility:
noise immunity
acc. to EN 61000-6-2
noise emission
acc. to EN 61000-6-4
Safety requirements:
Acc.to EN 61010-1:
isolation ensured by the housing:
double
isolation between circuits:
basic
Pollution degree:
2
For working voltages in relation to the
ground up to 300 V
installation category:
III
For working voltages in relation to the
ground up to 600 V
installation category:
II
Altitude above sea level:
< 2000 m
Reviews