AC Signal Transducer, P21Z – available on request
Description
PRODUCT DESCRIPTION
Measuring transducer P21Z type is destined to a continuous conversion of a.c. current or a.c. voltage without the constant component or frequency into a standard d.c. current or d.c. voltage signal or digital signal.
The transducer output signal is galvanically insulated from the input signal and the supply.
Features P21Z:
input:
100, 250, 400 V a.c.
1 A, 5A a.c.
20?50Hz
output:
0/4?20mA, 0?10V
RS-485? with Modbus protocol
programmable parameters by PD14 programmer and free eCon software
measurement averaging time,
converting characteristics
value of output signal when limit value are exceeded,
constraining output signal,
transmission parameters of RS485
external dimensions: 22,5 x 120 x 100mm.
?
SPECIFICATIONS
Inputs
Measuring ranges
Parameters
Overloads
0?1?100?130 V ac
input resistance > 2 M?
Short duration overload (1s): 2 Un
(<1000 V), 10 In 0?2.5?250?325 V ac 0?4?400?600 V ac 0?0.1?1.0?1.3 A ac input resistance 10 m? ? 10% Sustained overload: 150% Un (only for Un = 400 V and ? 400 V), 120% Un (for other Un), 120% In 0?0.05?5.0?6.3 A ac input resistance 2 m? ? 10% 20?500 Hz (in voltage range 24?480) input resistance > 2 M?
?
?
Outputs
Output kind
Properties
0?20?22 mA
Rload ? 250 ?
4?20?22 mA
0?10?11 V
Rload ? 500 ?
?
Digital interface
Interface type
Transmission protocol
Modes
Baud rates
RS-485
MODBUS RTU
8N2, 8E1, 8O1, 8N1
4.8, 9.6, 19.2 kbit/s
?
External features
Weight
< 0.125 kg
?
Dimensions
22.5 x 120 x 100 mm
?
Protection acc to EN 60529
Ensured by the housing: IP40
From the terminal side: IP 20
Fixing
35 mm rail
acc to EN60715
?
Rated operating conditions
Supply
85?253 V ac, 40?400 Hz; 90?300 V dc
20?40 V ac 40?400 Hz; 20?60 V dc
Power consumption < 3 VA
Temperature
Ambient -20?23?60 ?C
Storage -25?85 ?C
Relative humidity
< 95%
Inadmissible vapour condensation
Operating position
Any
?
Preheating time
15 min
?
Av time of the measurement
? 0.5 s
1 second set by default
?
Safety and compatibility requirements
Electromagnetic compatibility
Noise immunity
acc to EN 61000-6-2
Noise emissions
acc to EN 61000-6-4
Isolation between circuits
Basic
acc to EN 61010-1
Pollution grade
2
Installation category
III (for the 400 V option ? category II
Maximal phase-to-earth operating voltage
for the supply circuit 300 V
for the measuring input 600 V cat II
(300 V cat III)
for the programming input 50 V
for the output 50 V
Altitude above sea level
Reviews